1000kw-4000kw combustible heavy fuel oil generator sets are used for HFO power station(power plant)
Characteristics:
Meet with: ISO8528, IEC60034, ISO3046;
Marine medium speed engine driven, modular construction, Diesel/HFO burning;
Brushless self excited alternator with AVR;
Application: Marine AUX, Land (EPS) power, Containerized power.
Low noise, long TBO, low operating cost.
A. Standard generating set of 1MW HFO power plant(HFO Gensets):
1.Diesel engine, coupling and common base with std accessories including: Lube oil cooler, Lube oil filter, Fuel strainer, Manual pre-lubricating pump, Injector cooler, Control valve for turning, Adjusting pressure valve, High pressure air filter, Spare parts kit for turbocharger, Foundation bolt, Model CZ20/30 air compressor, Air bottle
2.Alternator
3.Switchgear including:1) VCB, 2) Protection, CT and PT, 3) Meters, indicators
4.Control and operation panel including:1) Programmable Logic Controller (PLC), 2)Automatic Voltage Regulator, 3) Meters, indicators, hour counters, 4) Push buttons, selector switches, 5) Auto synchronization and load-share device
5. Local control desk: 1) Pressure gauges, switches, 2) Temperature indicators or scanner, 3) Scanner for Engine exhaust temperatures, 4) Push buttons, indicating lamps, selector switches, 5) Flasher
B. Generating accessories:
1.Generating accessories including: Lube oil tank, Silencer, Exhaust pipe and elbow, Exhaust expansion joint Cooling tower, Thermostatic valves
C. Electricals:
1. PT for 15kV busbar (KYN28A-24)
2.Main outgoing panel for power transformer
3.Station transformer incoming and PT panel
4.220V/24VDC panel
5.400 Volt main panel
6.400 Volt supply panel to DG set auxilliaries
7.S9-160kVA/13.8/0.48kV station transformer
8.Synchronous cabinet
9.Cooling tower and air compressor control
Specifications of 1000KW HFO Generator Sets
Generator Model |
500GF |
600GF |
800GF |
1000GF |
1250GF |
Rated Genset Power(KW) |
500 |
600 |
800 |
1000 |
1250 |
Engine Model |
N6210ZD12 |
N6210ZD4 |
N6210ZD18 |
N8210ZD |
N8210ZD4 |
Bore x Stroke (mm) |
210x300 |
Engine Type |
4-Stroke, Inline, Direct Injection, Tubocharged, Intercooled |
Engine Capacity(KW) |
551 |
662 |
882 |
1103 |
1471 |
Engine Rev. (rpm)
|
50Hz@750
60Hz@720 |
50Hz@750
60Hz@720 |
50Hz@1000
60Hz@900 |
50Hz@1000
60Hz@900 |
50Hz@1000
60Hz@900 |
Fuel Consumption (L/h) |
131 |
154.3 |
207.6 |
261.9 |
327.4 |
Voltage |
Voltage no load adjustment range |
% |
95~105 |
Voltage fluctuation rate |
% |
±1 |
Stable voltage regulating rate |
% |
±2.5 |
Transient voltage regulating rate |
% |
±20~-15 |
Stabilizing time |
s |
1 |
Alternator Excitation method |
|
Brushless AVR |
Frequency |
Stable frequency (rev.) regulating rate |
% |
5 |
Frequency (rev.) fluctuation rate |
% |
±0.5 |
Transient frequency regulating rate |
% |
±10 |
Stabilizing time |
s |
< 5 |
Frequency regulating method |
|
Auto / Manual |
Protection |
Over speed: 115% Nr A, T, S Reverse P.: -9.6% Pn A, T |
LO. P : 0.25MPa A, 0.15MPa T,S Over current:130% In A, T |
FW T.: 90centigradeA, 95centigradeT,S Over voltage: 120% V A, T |
LO. T: 90centigradeA Over load:110% In A |