120KW Natural Gas/Biogas/Marsh Gas Generator Set
120KW Gas Generator sets:
Conditions for Using:
1. Temperature of the straw gas used in this biomass generator set should not surpass 40 Celsius when it is 1m or nearer to the pressure regulating valve for air inflow.
2. The pressure that this biomass generator set can sustain ranges from 3kPa to 10 kPa and the fluctuated frequency of the pressure should not surpass 1kPa/min.
3. The granularity of the impurity should not surpass 5 μ M and its max. Content is 30mg/Nm3.
4. For the straw gas used in this biomass generator set, the volume content of H2 should not surpass 20% and the max. Content of H2S, NH3 and tar are 50mg/Nm3, 20mg/Nm3, and 50mg/Nm3.
5. The moisture content in straw gas should not surpass 40g/Nm3 and the heating value of the straw gas should not lower than 4MJ/Nm3.
For gas that cannot reach the conditions above, special allocation will be took for this biomass generator set after evaluation according to the specific composition, pressure, temperature, etc. Provided.
The operating principle is as following:
After dewatered, decoked and then dust-abated, the marsh gas enters into the absorption tower, the CH4 viscosity of which, in the special condition and absorbent, is adjusted to 90%, meanwhile it is purified by eliminating partly or wholly impurities like ammonia, nitrogen, oxide, siloxane etc. The adjusted and purified gas will be output into natural gas network after cooling and separating. The liquid will separate the impurify by self-clearning system, and absorb CO2(purify≥ 95%) from renewable system.
Specifications of Gas Genset
Genset Model |
AVGH25-G |
AVGH50-G |
AVGH75-G |
AVGH120-G |
Genset Rated Power (kW/KVA) |
25/31 |
50/63 |
75/94 |
120/150 |
Engine Model |
HG4B |
HG6B |
HG6L |
HGN14 |
Engine Rated Power (KW) |
33 |
56 |
85 |
135 |
Type |
Inline, four stroke, electronic
control spark plug ignition,
water-cooling, dry cylinder
jacket, premix proper ratio of air and gas before combustion |
Inline, four stroke, electronic
control spark plug ignition,
water-cooling, wet cylinder jacket,
premix proper ratio of air and
gas before combustion |
Cooling mode |
Radiator fan cooling for closed-type cooling mode,
or heat exchanger water cooling for cogeneration unit |
Cylinders&Arrangement |
4L |
6L |
6L |
6L |
Bore x Stroke (mm) |
102*120 |
102*120 |
114*135 |
140*152 |
Displacement (L) |
3.92 |
5.88 |
8.3 |
14 |
Compression ratio |
11.5:1 |
11.5:1 |
11.5:1 |
11.5:1 |
Rated speed (r/min) |
1500 |
Fuel |
Natural gas or biogas |
Gas consumption ratio (g/kWh ) |
≤ 230 g/kWh ( 0.30 m3/kW@h) (97% natural gas) |
Ignition order |
1-3-4-2 |
1-5-3-6-2-4 |
1-5-3-6-2-4 |
1-5-3-6-2-4 |
Idling speed ( r/min ) |
700 |
Oil recommended |
SAE 15W/40CD CNG special lube oil |
Oil consumption |
≤1.0g/kW.h |
The highest exhaust (C ) |
≤600 |