Max.PV Power: | 11kwp |
---|---|
Max.Permitted DC Voltage: | 880VDC |
Mpp Voltage Range: | Input Short-Circuit Current |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
PV side | |
Max.PV power | 11kWp |
Max.permitted DC Voltage | 880Vdc |
Input short-circuit current | 31.25A |
Max.permitted DC current | 25A |
Input points | 2 |
MPPT voltage range | 420~820Vdc |
PV Start Voltage | 465Vdc |
MPPT efficiency | 99.9% |
Max Inverter feedback Current to the array | 0A |
Grid side | |
Rated output power | 10kW |
Max.output current | 15.2A |
THD of grid current | <3% |
Power factor | >0.99 |
Max.efficiency | 95.00% |
European efficiency | 94% |
Permitted grid voltage range | 320~450Vac 3~ |
Permitted grid frequency range | 47.5~51.5Hz |
Standby power consumption | <30W |
Nighttime power consumption | <20W |
Grid monitoring | According to VDE0126-1-1 guidelines |
Communication interface | RS485/Ethernet(optional)/GPRS/(optional) |
Man-machine interface | LCD |
Mechanical | |
Dimensions(M×H×D) | 610×1420×600 mm |
Weight | 302kg |
Environmental conditions and safety | |
Protection level | IP20 |
Cooling | Air cooling |
Operating temperature range | -25~+55'C |
Relative humidity range | 15-95% (non condensing) |
Mounting altitude | 3000m;above 3000mneed derate operating |
Noise emissions | <65dB |
Meet the standards | EN 50178;DIN EN 62109; prlEC 62109-2; VDE 0126-1-1(or CGC/GF001:2009); EN6100-6-2 2005; EN6100-6-4 2007; ENEL(Italy);G59/2(UK); |